Floor Perimeter Demarcation Lines

title: General Requirements
body: Outlines the egress path using low-location photoluminescent lines on both sides of the path.
spec: Width | Min 1″ — Max 2″
spec: Continuity | Max 4″ gap to accommodate conduits, moldings, corners, or bends
spec: Consistency | Uniform and consistent throughout the same exit
—
fig: Fig. 7
cap: Floor Mounted
app: Option A — 2.2.4.1 Floor Mounted
title: Floor Mounted Demarcation
body: Placed as close as practicable to the wall. Extends within 2″ of landing leading-edge markings. Continues across the floor in front of all doors (except those with door frame markings per 2.2.9.3). May route around obstructions such as standpipes so the obstruction is outside the outlined area.
—
fig: Fig. 8
cap: Routing Around Obstruction
app: Option A — Obstruction Routing
title: Floor Mounted — Obstruction Detail
body: Where an obstruction such as a standpipe is located within the egress path, the demarcation line may extend across the floor so that the obstruction is outside of the outlined area.
—
fig: Fig. 9
cap: Wall Mounted
app: Option B — 2.2.4.2 Wall Mounted
title: Wall Mounted Demarcation
body: Bottom edge no more than 4″ above finished floor. At top or bottom of stairs, drops vertically to floor within 2″ of step/landing edge. Continues across the face of all doors or transitions to the floor in front of such doors. May transition to floor where wall-mounting is impractical.
—
fig: Fig. 10
cap: Transition to Floor
app: Option B — Transition Detail
title: Wall to Floor Transition
body: Demarcation lines on walls shall transition vertically to the floor and then extend across the floor where a line on the floor is the only practical method of outlining the egress path.
note: Exceptions — Not Required | 1. On the sides of steps. 2. Where an area is not part of the egress path (e.g., obstructions or dead ends).